SCOPE CIRCUIT BREAKER TESTING HISAC ULTIMA WITH DCRM+

Specifications

  • Trigger Options : O, C, C-O, O-C, O-C-O
  • Timing Channel : 24 : 4 Main + 4 PIR per pole, 3 poles Simultaneously
  • Auxiliary Contact Timing Channel : 8 : 4 dry + 4 wet Expandable up to 6 Dry + 6 Wet
  • Coil Current Channel : 3 : Trip / Close coil current optionally expandable up to 6
  • Travel Channel : 3 : Travel characteristic optionally expandable up to 6
  • Analog Channel for DCRM Input (Optional) : 2 / 4 / 6 – as per DCRM modules selected
  • DCRM Resistance Range & Current (Optional) : 1000 / 2000 / 4000 / 8000 μΩ Selectable, Current 100A DC
  • Static Contact Resistance (CRM) Channel : As per DCRM modules selected
  • CRM Resistance Range : 1000 / 2000 / 4000 / 8000 μΩ Selectable
  • Sampling Speed : 1 / 2 / 5 / 10 / 20 kC Selectable
  • Power : 230 V AC ± 15% , 50Hz ± 10%