SCOPE TRANSFORMER TURNS RATIO METER - TTRM 302

Specifications

  • No of channels : Three HV channels and three LV channels
  • Test Voltages : 10V, 40V and 100V AC selectable voltages
  • Measurements : Ratio, Ratio error, Phase Angle Deviation, Excitation current, Vector group and Magnetic balance (optional)
  • OLTC Control : Raise and Lower control to operate OLTC
  • Test Results Display : 5.7” touch-screen (TFT) display, thermal printer
  • Test Leads : Suitable to test EHV Transformers
  • Paper : Thermal, 58 mm wide roll form
  • Memory : Up to 50000 records inbuilt memory, with date and time stamping
  • Power : (110V ± 15%) / (60Hz ± 10%) OR (230V ± 15%) / (50Hz ± 10%), 75VA.
  • Communication Port : Ethernet port for PC Communication, USB port for data downloading to pen-drive
  • Housing : IP 65 rated moulded case
  • Operating Environment : -20°C to +55°C, 95%RH (non-condensing)
  • Storage Environment : -40°C to +60°C, 95%RH (non-condensing)
  • Dimensions : 435 X 315X 175 mm. (Max.)