HISAC Swift

Circuit Breaker Operational Analyser

SCOPE offers HISAC Swift – Circuit Breaker Operational Analyser for checking the performance of the circuit breakers. The Analyser contains various intelligent measuring modules designed for measuring parameters such as contact timings of Main, PIR & Auxiliary Contacts, Close & Trip Coil Current characteristics and Static Contact Resistance of three poles simultaneously. The results can be directly viewed on the TFT touch screen display in graphical as well as numerical form. It is possible to print the graph on built-in thermal printer or download record to computer for further analysis on CPLOT software. All these facilities in one instrument make it best suited for gang operated CBs.
  • Operations: C, O, C-O, O-C, O-C-O with configurable delays and Static Contact Resistance
  • When Setup manu is invoked through the touch-screen keyboard, it is possible to access saved system settings and data of Breaker under test
  • Contact Timing: Channels for 3 Main, 3 PIR & 2 Auxiliary (Wet / Dry) Contacts with 05mS resolution
  • Coil Current: One internal channel to measure Close and Trip coil current
  • Three multiplexed channels to measure Static Contact Resistance up to 2Ω with resolution of 1μΩ
  • TFT color graphical display with touch screen displays test settings, numerical & graphical test results with full resolution
  • Printout through inbuilt, 58mm thermal printer for printing test header, graph and calculations
  • Provided with in-built memory to store up to 100 records
  • WindowsTMbased CPLOT software to download the record to computer through USB connectivity for further analysis & storage
  • Type Tested as per IEC 60068-2, IEC 61326-1 & IEC 61010-1. CE marked

TECHNICAL DATA

Full Product Specifications

SpecificationsBreaker Control : Two solid state contacts rated at 50A, 300V AC/DC for breaker operation
ChannelsConfigurationRangeResolutionAccuracy
Contact Timing Channels6 : 1 Main + 1 PIR

per pole, 3 poles

Simultaneously

Measurement duration

1mS to 4S @ 1kC,

0.05mS to 200mS @ 20kC

1mS @ 1kC

0.05mS @ 20kC

Value ± 0.05%

± resolution

Auxiliary Contact Timing

Channels

 

2 : Dry / Wet Selectable

15 to 300V DC

(for Wet Channels)

1mS @ 1kC

0.05mS @ 20kC

Value ± 0.05%

± resolution

Coil Current

Channel

1 : Trip / Close coil current1, 2, 5, 10, 25, 50 A DC0.1% of selected rangeValue ± 1%

± resolution

Contact Res.

Channels

3 : Multiplexed 3 Channels.

10 A Max.

200μΩ,             2000μΩ,          20mΩ,

200mΩ & 2Ω – Auto ranging

0.1μΩ @ 200μΩValue ± 2%

± 5 x resolution

  • Sampling Speed : 20kC, 10kC, 5kC, 2kC & 1kC, selectable
  • Plot Length : 200mS at 20kC, 400mS at 10kC, 800mS at 5kC, 2000mS at 2kC and 4000mS at 1kC
  • Display : 320 x 240 pixel, 7” colour TFT LCD with touch screen
  • Printer : 58 mm paper width, in-built thermal printer
  • Environment : 0 to 50°C, 95% RH (non condensing)
  • Power : 94 – 264 V AC, 50/60 Hz ± 10%, 110 VA

Related Products

Multifunctional analyzer EVSE-100 is an instrument dedicated to diagnostics of electric vehicle charging stations and cables. Using a single device, we will perform a set of tests on these objects, ending with the generation of a professional report. Through appropriate simulation of CP and PP circuits, the meter can put the station into various operating states. This allows us to verify the correctness of the control system and perform measurements in the field of electric shock protection. We can complete the verification of functionality and safety by simulating errors on the power supply side, i.e. the charging station (ICCB), and charging side of the vehicle (CP circuit)
After excavation, sometimes it is confusing to identify the right cable from bunch of similar appearance cables. Cable identification is very important for safety of field personnel – Cutting a wrong cable can be fatal. So, we require a Cable Identification System having current direction facility to identify the wanted cable.Cable Identification is the most critical and safety related sequence during all the procedure of cable fault location. The correct identification of a cable out of a bundle of cables, where most of them can be cables in service, has to be carried out not only carefully, but also by means of an instrument widely eliminating the possibility of human error or misinterpretation.The Cable Identification System, CFL CIS from SCOPE is the ultimate solution for identifying wanted cable from a bunch of cables in a trench, pit or cable rack. The SCOPE’s Cable Identification System CFL CIS is designed to fulfill these most important safety aspects.
HPT Series Hi-Pot Test Sets is available in three different combinations, viz., Power Frequency AC, DC and AC-DC Combined HV Test Sets for testing of transformers, motors, insulators, cables etc. Further, these test sets are capable of giving continuously variable HV from zero to maximum rated output voltage.HPT Series testers are specifically designed for safe and accurate measurement of leakage current to evaluate insulation integrity. These testers are moveble, one end ground test systems, ideal for HV testing. Accurate leakage measurements are ensured by placing the current meter in the return path of the HV. Years of Design, engineering and manufacturing experience have made our HPT testers the most durable, easily operated and the best designed sets in the segment. The product has been designed considering the importance of safety of the operator. The kit has various interlock to avoid any kind of accident while doing the high voltage testing.
SCOPE offers its modern generation of iconic SCOT Series Circuit Breaker Time Interval Meters in all new super-light avatars, based on cutting edge micro controllers & powered by embedded technology.User can choose from two models, SCOT M3K+ and SCOT MXP+ depending on type of circuit breaker and testing to be done.