CFL Series – CIS

Cable Identification System: CFL CIS

After excavation, sometimes it is confusing to identify the right cable from bunch of similar appearance cables. Cable identification is very important for safety of field personnel – Cutting a wrong cable can be fatal. So, we require a Cable Identification System having current direction facility to identify the wanted cable.Cable Identification is the most critical and safety related sequence during all the procedure of cable fault location. The correct identification of a cable out of a bundle of cables, where most of them can be cables in service, has to be carried out not only carefully, but also by means of an instrument widely eliminating the possibility of human error or misinterpretation.The Cable Identification System, CFL CIS from SCOPE is the ultimate solution for identifying wanted cable from a bunch of cables in a trench, pit or cable rack. The SCOPE’s Cable Identification System CFL CIS is designed to fulfill these most important safety aspects.
  • User Friendly LED Indication for Right & Wrong Cable Identification from multiple cables
  • Flexible coil is thin, flexible for easy insertion between closely mounted conductors or where access is restricted and provided with locking facility for contact firmness
  • Two different ranges of pulse current which enables the accurate Cable Identification in all types power cables
  • 10 Stages Amplifier Setting for Better Signal Receiving
  • Operation Via both Mains Supply and Internal Li-Ion Rechargeable battery
  • Compact, Light Weight, water resistant and dust proof design
  • Belt arrangement for receiver to easy carrying
  • User friendly and simple operation

TECHNICAL DATA

Full Product Specifications

ParametersCFL CIS
Pulse Voltage55VDC / 36VDC
Pulse Current100A / 60A
Pulse Sequence30 pulses/ min, User configurable
Pulse Width72ms
Power Supply100 to 265 VAC 50/60Hz
Battery11.1 V Li-ion Rechargeable Battery
Operating Time6 Hours
Weight6 Kg approx.
Dimension339mm x 295mm x 152 mm
Environmental-20°C to +55 °C, 95% RH(Non-Condensing)

 

ParametersCFL CIS-R
Display TypeLED scale
Flexible Clamp150mm Diameter
Sensitivity100% at 31.25Ω loop resistance
Amplifier Setting10 stages
Battery11.1 V Li-ion Rechargeable Battery
Operating Time8 Hours
Weight0.7 Kg approx.
Dimension210mm x 124mm x 51 mm
Environmental-20°C to +55 °C, 95% RH(Non-Condensing)

Related Products

HISAC Ultima – new generation Circuit Breaker Dynamic Test Set from SCOPE …. The ultimate solution for testing Circuit Breakers of all types. HISAC Ultima is the most complete analyser for checking the dynamic performance of CBs in live EHV switchyards upto 765 kV.HISAC Ultima can carry out Dynamic Contact Resistance Measurement on SIX breaks of THREE poles in one operation thereby significantly reducing stress on CB & testing downtime.HISAC Ultima with DCRM+ ensures end users safety by providing Dual Earth Test, in which Circuit Breaker will be grounded from both sides while conducting the test.It offers flexibility to create pre-programmed Test Plans including all test settings for all types of circuit breakers available in a switchyard that can simply be recalled at the time of actual testing. This saves you from doing all settings in switchyards.The Analysis software offers a range of utilities which enables effective Condition Monitoring of CB by comparing present test data with previous signatures and predicting future performance.
CFL PL Series, Cable Fault Pre-Locators from SCOPE are the ultimate solution for locating underground cable faults in minimum time.
HPT Series Hi-Pot Test Sets is available in three different combinations, viz., Power Frequency AC, DC and AC-DC Combined HV Test Sets for testing of transformers, motors, insulators, cables etc. Further, these test sets are capable of giving continuously variable HV from zero to maximum rated output voltage.HPT Series testers are specifically designed for safe and accurate measurement of leakage current to evaluate insulation integrity. These testers are moveble, one end ground test systems, ideal for HV testing. Accurate leakage measurements are ensured by placing the current meter in the return path of the HV. Years of Design, engineering and manufacturing experience have made our HPT testers the most durable, easily operated and the best designed sets in the segment. The product has been designed considering the importance of safety of the operator. The kit has various interlock to avoid any kind of accident while doing the high voltage testing.
SCOPE’s Single Phase (TTRM 101 / TTRM 102) and Three Phase (TTRM 301 / TTRM 302), Transformer Turns Ratio Meters are rugged yet light weight and highly reliable instruments to measure turns ratio of transformers in live switchyards up to 765kV.TTRM is equally suitable for use on manufacturing shop floor and test laboratories. It can be used for testing of single / three phase power transformers (star or delta connected, with or without neutral), CTs and PTs.